Item |
Type B RCD / Type B RCCB |
Product Model |
EKL6-100B |
Type |
B Type |
Rated Current |
16A , 25A , 32A , 40A , 63A , 80A ,100A |
Poles |
2Pole ( 1P+N ) , 4Pole ( 3P+N ) |
Rated voltage Ue |
2Pole: 240V ~ , 4Pole: 415V~ |
Insulation Voltage |
500V |
Rated frequency |
50/60Hz |
Rated residual operation current(I n) |
30mA , 100mA , 300mA |
Short-circuit current Inc= I c |
10000A |
SCPD fuse |
10000 |
Break time under I n |
≤0.1s |
Dielectric test voltage at ind.Freq. for 1min |
2.5kV |
Electrical life |
2,000 Cycles |
Mechanical life |
4,000 Cycles |
Protection Degree |
IP20 |
Ambient temperature |
-5℃ upto +40℃ |
Storage temperature |
-25℃ upto +70℃ |
Terminal connection type |
Cable/Pin type busbar
U-type busbar |
Terminal size top/bottom for cable |
25mm² 18-3AWG |
Terminal size top/bottom for busbar |
25mm² 18-3AWG |
Tightening torque |
2.5Nm 22In-Ibs |
Mounting |
On DIN rail EN60715(35mm)
by means of fast clip device |
Connection |
From top and bottom |
Standard |
IEC 61008-1:2010 EN 61008-1:2012
IEC 62423:2009 EN 62423:2012 |